HomeRecall categoriesIndustrial, businessSafety equipmentTyco Australia Pty Ltd—Vigilant F3200 Fire Indicator Panel MAF/PSU Module Fitted with "Dong Woo" Signalling Relays

Tyco Australia Pty Ltd—Vigilant F3200 Fire Indicator Panel MAF/PSU Module Fitted with "Dong Woo" Signalling Relays

PRA number: 2009/10822
Date created: 22nd May 2009

Product information

Product description

Vigilant F3200 Fire Indicator Panel MAF/PSU Module Fitted with "Dong Woo" Signalling Relays manufactured during 2005-2007 inclusively.

Identifying features

NA

What are the hazards?

Fire

What are the defects?

There is the potential for a latent fault to develop within F3200 Fire Alarm panels installed with a MAF/PSU module fitted with "Dong Woo" brigade signalling relays.If the fault develops and the relay fails, the fire alarm panel will fail to send an automated signal to the fire department and/or monitoring centre that the fire alarm has been activated.

Dates available for sale

  • 2nd January 2005 - 31st December 2007

Where the product was sold

  • National

Supplier

Tyco Australia Pty Ltd

What should consumers do?

Contact Tyco F3200 Customer Service on 1300 721 517 for a Return Authorisation Number (RAN) and a claim form. Complete the claim form and return to the address listed on the top of the claim form.